Menu Bar Function 6
6-46
* In the printer GT-10A, set the switch (SW1-1) on the serial communication board to ON to select the
general-purpose printer mode.
* The speed "19,200 bps" is supported in the DU/WIN-E V 2.2 or later.
(It is supported only in the GOT. It is not supported in the DU (50DU-TK.))
7 ) DU Menu Key
Set the position of the touch key to call the system menu of the DU.
8 ) Bar Code Settings
Set the head word device No. and the number of word devices of the PLC to which the data read by the
bar code reader connected to the GOT in serial communication (RS-232C) is written.
(For the F930GOT, this item is supported in V 2.3 or later.)
a) Use Bar Code
Click to check the check box to connect a bar code reader.
b) Head Address
Input the head device No. of the PLC to which the data is written.
Available word devices are only the current values in which a numeric value from 0 to FFFFH can be
handled.
T, C, D - - - - - - - - - -FX Series
D, W, T, C, R, Z, V - -A/QnA/Q Series
D - - - - - - - - - - - - - -General-purpose communication
D - - - - - - - - - - - - - -OMRON C Series, Siemens S7-300 Series
c) Nbr of Addresses
Set the number of word devices (from 2 to 32) beginning with the word device No. set in "2) Head
Address" to be used in communication.
Data format1st word device = Bar code data size
2nd word device and later = Bar code data
Position
Select either one among "None", "UpLeft", "LowLeft",
"UpRight" and "LowRight".
When turning on the power while pressing and holding the touch key set in "Position" of "DU Menu Key",
the system menu of the DU is displayed.
50DU-TK
F940GOT
Position
Select one or two among "None", "UpLeft", "LowLeft",
"UpRight" and "LowRight".
When a touch key set in "Position" on the Menu Key screen is pressed while the user screen is
displayed, the main menu screen of the F940GOT is displayed.
a) Use Bar Code
b) Head Address
c) Nbr of Addresses