8. Spindle Parameters
8.3 MDS-B-SP/SPH, MDS-C1-SP/SPH
213
No. Items Details
Setting
range
Standard
setting
3263
(PR)
SP063 OLT Overload
alarm
detection time
Set the time constant for detection of the
motor overload alarm.
0 to 1000
(s)
60
3264
(PR)
SP064 OLL Overload alarm
detection level
Set the detection level of the motor overload
alarm.
0 to 120
(%)
110
3265
(PR)
SP065 VCGN1 Target value of
variable speed
loop
proportional
gain
Set the magnification of speed loop
proportional gain with respect to SP022
(VGNP1) at the maximum motor speed
defined in SP017 (TSP).
0 to 100
(%)
100
3266
(PR)
SP066 VCSN1 Change
starting speed
of variable
speed loop
proportional
gain
Set the speed when the speed loop
proportional gain change starts.
SP066 SP017
SP022
SP022×
(SP065/100)
Proportional gain
Speed
0 to 32767
(r/min)
0
3267
(PR)
SP067 VIGWA Change
starting speed
of variable
current loop
gain
Set the speed where the current loop gain
change starts.
0 to 32767
(r/min)
0
3268
(PR)
SP068 VIGWB Change
ending speed
of variable
current loop
gain
Set the speed where the current loop gain
change ends.
0 to 32767
(r/min)
0
3269
(PR)
SP069 VIGN Target value of
variable
current loop
gain
Set the magnification of current loop gain
(torque component and excitation
component) for a change ending speed
defined in SP068 (VIGWB).
When this parameter is set to "0", the
magnification is 1.
SP067 SP017SP068
Speed
1-fold
SP069×(1/16)-fold
0 to 32767
(1/16-fold)
0
SP017 (TSP)
Maximum
motor speed
SP067
(VIGWA)
SP068
(VIGWB)
SP069
(VIGN)
0 to 6000 0 0 0
6001 to 8000 5000 8000 45
8001 or more 5000 10000 64