Mitsubishi Electronics SW8D5C-GPPW-E Child Tracker User Manual


 
2 - 1 2 - 1
2 SYSTEM CONFIGURATION
MELSOFT
2. SYSTEM CONFIGURATION
This section explains the system configuration to connect GX Developer and a safety
CPU.
For details of connection cable, refer to GX Developer Version 8 Operating Manual.
2.1 Connecting to Safety CPU
The following explains the system configuration when GX Developer is connected to
a safety CPU.
(1) Direct coupling to a safety CPU
USB cable
Programmable controller
direct coupled
(USB communication)
Safety CPU
GX Developer
(a) Compatible GX Developer
Use the GX Developer Version 8.40S or later.
(2) Connecting via Ethernet, CC-Link IE Controller Network, MELSECNET/H
*1
Via network
GX Developer
Ethernet
CC-Link IE
Control network
MELSECNET/H
Safety CPU
*1: For details of connecting a personal computer to each network, refer to the following manual.
GX Developer Version 8 Operating Manual
(a) Compatible GX Developer
Via QCPU:
Use the GX Developer Version 8.65T or later.
Via LCPU:
Use the GX Developer Version 8.88S or later.
Via safety CPU:
Use the GX Developer Version 8.98C or later.
(b) Compatible safety CPU
Via QCPU or LCPU:
Use safety CPU whose first 5 digits of the serial number are "10032" or
later.
Via safety CPU:
Use safety CPU whose first 5 digits of the serial number are "10042" or
later.
2