Section 1
General Information
Appendix A-5MN722
Table A-3 Power Output Parameter Block Values Level 2
Level 2 Blocks
Block Title Parameter P# Adjustable Range Factory User
Setting
OUTPUT LIMITS OPERATING ZONE 2001 1–STD CONST TQ
2–STD VAR TQ
3–QUIET CONST TQ
4–QUIET VAR TQ
STD
CONST TQ
MIN OUTPUT SPEED 2002 0-MAX Speed RPM 0 RPM
MAX OUTPUT SPEED 2003 0-30000 RPM Rated Motor
Speed
PK CURRENT LIMIT 2004 0-PEAK RATED CURRENT PK Control
Rating
PWM FREQUENCY 2005 1.0-5.0 KHZ (Standard)
1.0-16.0 KHZ (Quiet)
2.5 KHZ
CUR RATE LIMIT 2006 0.001-10.000 SEC 0.004 SEC
CUSTOM UNITS DECIMAL PLACES 2101 0-5 5
VALUE AT SPEED 2102 0-65535 / 0-65535 00000/
01000 RPM
UNITS OF MEASURE 2103 Selection of 9 Character Sets -
PROTECTION OVERLOAD 2201 0–FOLDBACK, 1–FAULT FOLDBACK
EXTERNAL TRIP 2202 0–OFF, 1– ON OFF
LOCAL ENABLE INP 2203 0–OFF, 1– ON OFF
FOLLOWING ERROR 2204 0–OFF, 1– ON OFF
TORQUE PROVING 2205 0–OFF, 1– ON OFF
MISCELLANEOUS RESTART AUTO/MAN 2301 0–MANUAL, 1–AUTOMATIC MANUAL
RESTART FAULT/HR 2302 0-10 0
RESTART DELAY 2303 0-120 SECONDS 0 SEC
FACTORY SETTINGS 2304 0–NO, 1–YES NO
HOMING SPEED 2305 0-MAX Speed 100 RPM
HOMING OFFSET 2306 0-65535 Encoder Counts 1024 CNTS
SECURITY
CONTROL
SECURITY STATE 2401 0–OFF
1–LOCAL SECURITY
2–SERIAL SECURITY
3–TOTAL SECURITY
OFF
ACCESS TIMEOUT 2402 0-600 SEC 0 SEC
ACCESS CODE 2403 0-9999 9999
MOTOR DATA MOTOR VOLTAGE 2501 150-999 VOLTS Factory Set
MOTOR RATED AMPS 2502 0-999.9 Factory Set
MOTOR RATED SPD 2503 0-32767 RPM 1750 RPM
MOTOR RATED FREQ 2504 0-500.0 Hz 60.0 Hz
MOTOR MAG AMPS 2505 0-0.54 AMPS CALC
ENCODER COUNTS 2506 0-65535 CNTS 1024 PPR
RESOLVER SPEEDS 2507 0 to 10 1 SPEED
CALC PRESETS 2508 0–NO, 1–YES NO