Using a Quantum 984 HSBY System
840 USE 106 00 January 2003 89
Therefore, the number you specify for the command register must be in the range
of 4x registers you specify in the State RAM area in State RAM dialog. If you are
using the 12K option, the command register must be one of the first 9000 4x
registers.
The command register must not be within the range of the nontransfer area,
which you specify in the nontransfer area of the Hot Standby dialog.
CAUTION
Hot Standby Command Register Hazard
Be sure the register you select as the Hot Standby command register is
reserved for this purpose and not used for other purposes elsewhere in
user logic.
Failure to follow this precaution can result in injury or equipment
damage.
CAUTION
Hot Standby Dialog Hazard
If you intend to use the Hot Standby dialog to configure the command
register and the CHS instruction to modify the command register during
runtime, make sure that you specify the same register as the command
register in Hot Standby dialog and the top node of the CHS block. If you
use different numbers for the command register, the changes that you
make via the Zoom screen are not applied to the real Hot Standby
command register.
Failure to follow this precaution can result in injury or equipment
damage.