Com Act Error Patterns
210
840 USE 106 00 January 2003
CHS 110 Hot Standby Module Error Patterns
CHS 110 Error
Patterns
The following table shows the number of times the Com Act indicator blinks for each
type of error and the codes possible for that group (all codes are in hex).
Number Blinks Code Error
1 6900 error in additional transfer calculation
2 6801 ICB frame pattern error
2 6802 head control block error
2 6803 bad diagnostic request
2 6804 greater than 128 MSL user loadables
4 6604 powerdown interrupt error
4 6605 UART initialization error
5 6503 RAM address test error
6 6402 RAM data test error
7 6301 PROM checksum error
8 C101 no hook timeout
8 C102 read state RAM timeout
8 C103 write state RAM timeout
8 C200 powerup error