Schneider Electric 840 USE 106 0 Stroller User Manual


 
Installation
62
840 USE 106 00 January 2003
The following diagram illustrates installation of a Hot Standby System.
Setting
Designation
Slide Switches
The designation slide switch on one Hot Standby module is set to A and the other is
set to B.
Connect Network The following diagram shows how to connect the network.
CAUTION
HAZARD
Before installing any controller in your Hot Standby system, be sure its
battery has been disconnected for at least five minutes.
Failure to follow this precaution can result in injury or equipment
damage.
Note: Be sure your system meets the power and grounding guidelines outlined in
Appendix D of the Quantum Automation Series Hardware Reference Guide, 840
USE 100 00.
Step Action
1 Install a splitter and a self-terminating F adapter between the primary RIO head
processor and the RIO network.
2 Connect the coaxial cable link.
3 Connect the cable between the splitter, another self-terminating F adapter and
the standby RIO head processor