Theory of IEC HSBY Operation
840 USE 106 00 January 2003 51
State Ram Transfer and Scan Time
Reduce Scan
Time
The state RAM transfer area contains all the state RAM values that are passed
between the Primary and Standby controllers. The size of the transfer area is as
large as the total size of your controller’s state RAM.
As the simplified block diagram below shows, all 0x references in the state RAM
transfer area are transferred first, then all 1x references, followed by all the 3x
references, and finally all the 4x references.
In the Quantum HSBY system, IEC HSBY does not allow customizing the transfer
area. This means the whole state RAM is transferred in IEC HSBY, except for the
nontransfer area, an area contained within the transfer area but ignored during the
actual state RAM transfer. Placing registers in the nontransfer area is one way to
reduce scan time because the Primary controller to CHS transfer time is shorter.
With Concept 2.5, a new function called Section Transfer Control has been added
which can be used to reduce scan time. See
Section Transfer Control, p. 135
for
further information on this feature.
Note: No matter how long your transfer takes, it does not cause a watchdog
timeout.