Transferring Additional State RAM Data
Additional Data If the Transfer Additional State RAM check box is activated, additional State RAM
could be transferred.
In the Additional State RAM area, enter the number of 0x, 1x, 3x, and 4x data
references that you want to be transferred as additional state RAM. All reference
data items must be specified in multiples of 16. You must enter a value of 16 or
greater for at least one of the four reference data types.
Use the Extra Transfer Time entry field to specify the number of scans over which
you want the additional data to be transferred. In general, the system divides the
number of reference data elements specified in the fifth entry field by the number of
scans specified in the sixth entry field. Accordingly, it divides the data into groups
that are transferred contiguously over the specified number of scans. These groups
of data are transferred with the regular state RAM data that has been scheduled on
every scan.
CAUTION
Transfer Additional State RAM Hazard
If you choose Transfer Additional State RAM, you must specify
additional data to be transferred or the controller will not start.
Failure to follow this precaution can result in injury or equipment
damage.