State Industries GFK-0827 Bottle Warmer User Manual


 
3
48 Series 90-70 Hot Standby CPU Redundancy User’s Guide – December 1993
GFK-0827
Configure a Genius Bus Controller
To configure a Genius Bus Controller module in rack 0, slot 3, position the cursor on slot
3 and press the genius softkey (F2). To display the catalog list for the Genius Bus
Controller, press the gbc softkey (F1). Press the Enter key to select the Genius Bus
Controller module. The Genius Bus Controller detail screen will then be displayed as
shown below.
To change the Genius bus redundancy mode for redundancy, move the cursor to
Redund Mode: Press the Tab key until the value for the field changes to RED CTRL.
Note that in a Hot Standby CPU Redundancy system, the only values that are valid for
this parameter are NONE or RED CTRL.