5.7.4 Setting communication monitoring for I/O scanning
WARNING
LOSS OF CONTROL
The product is unable to detect an interruption of the network link if
connection monitoring is not active.
Verify that connection monitoring is on.
The shorter the time for monitoring, the faster the detection of the
interruption.
Failure to follow these instructions can result in death, serious
injury or equipment damage.
Communication monitoring for I/O scanning is set by means of the
parameter EthMbScanTimeout.
Set communication monitoring for I/O scanning with the parameter
EthMbScanTimeout.
Parameter name
HMI menu
HMI name
Description Unit
Minimum value
Factory setting
Maximum value
Data type
R/W
Persistent
Expert
Parameter address
via fieldbus
EthMbScanTimeou
t
Modbus TCP I/O scanning timeout
Communication monitoring timeout for Mod-
bus TCP.
Value 0: Timeout monitoring disabled
In increments of 0.1 s.
Changed settings become active immedi-
ately.
s
0.0
2.0
60.0
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:2D
h
Modbus 17498
Profibus 17498
CIP 168.1.45
5.8 Setting the web server
The web server is activated or deactivated by means of the parameter
EthWebserver.
If you do not want to use the web server, set the parameter
EthWebserver to "Off".
See chapter "6.3.1 Web server" for additional information on the web
server.
Parameter name
HMI menu
HMI name
Description Unit
Minimum value
Factory setting
Maximum value
Data type
R/W
Persistent
Expert
Parameter address
via fieldbus
EthWebserver Ethernet webserver
0 / Off: Ethernet webserver off
1 / On: Ethernet webserver on
Changed settings become active the next
time the product is switched on.
-
0
1
1
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:6
h
Modbus 17420
Profibus 17420
CIP 168.1.6
LXM32M
5 Commissioning
Modbus-TCP module
49
0198441113843, V1.01, 01.2012