Schneider Electric LXM32M Card Game User Manual


 
5.6 Master with Word Swap
The IP address of a master with Word Swap is set by means of the
parameters EthMbIPswap1 ... EthMbIPswap4.
You may not set an IP for a master without Word Swap.
Check whether or not the master uses Word Swap.
If the master uses Word Swap, set the IP address of the master
with the parameters EthMbIPswap1 ... EthMbIPswap4.
Parameter name
HMI menu
HMI name
Description Unit
Minimum value
Factory setting
Maximum value
Data type
R/W
Persistent
Expert
Parameter address
via fieldbus
EthMbIPswap1 IP address of master for Modbus word
swap, byte 1
IP address of a Modbus master device. For
this master, the word order is swapped to
"Low word first", instead of the default "High
word first".
High word first -> Modicon Quantum
Low word first -> Premium, HMI (Schneider
Electric)
Changed settings become active immedi-
ately.
-
0
0
255
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:50
h
Modbus 17568
Profibus 17568
CIP 168.1.80
EthMbIPswap2 IP address of master for Modbus word
swap, byte 2
Changed settings become active immedi-
ately.
-
0
0
255
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:51
h
Modbus 17570
Profibus 17570
CIP 168.1.81
EthMbIPswap3 IP address of master for Modbus word
swap, byte 3
Changed settings become active immedi-
ately.
-
0
0
255
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:52
h
Modbus 17572
Profibus 17572
CIP 168.1.82
EthMbIPswap4 IP address of master for Modbus word
swap, byte 4
Changed settings become active immedi-
ately.
-
0
0
255
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:53
h
Modbus 17574
Profibus 17574
CIP 168.1.83
LXM32M
5 Commissioning
Modbus-TCP module
45
0198441113843, V1.01, 01.2012