Parameter name
HMI menu
HMI name
Description Unit
Minimum value
Factory setting
Maximum value
Data type
R/W
Persistent
Expert
Parameter address
via fieldbus
EthOptMapInp1 Optionally mapped input parameter 1 (drive
to PLC)
Modbus address of parameter which is
optionally mapped to Ethernet/IP assembly
or Modbus TCP I/O scanner data (drive to
PLC).
Changed settings become active immedi-
ately.
-
-
0
-
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:34
h
Modbus 17512
Profibus 17512
CIP 168.1.52
EthOptMapInp2 Optionally mapped input parameter 2 (drive
to PLC)
Modbus address of parameter which is
optionally mapped to Ethernet/IP assembly
or Modbus TCP I/O scanner data (drive to
PLC).
Changed settings become active immedi-
ately.
-
-
0
-
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:35
h
Modbus 17514
Profibus 17514
CIP 168.1.53
EthOptMapInp3 Optionally mapped input parameter 3 (drive
to PLC)
Modbus address of parameter which is
optionally mapped to Ethernet/IP assembly
or Modbus TCP I/O scanner data (drive to
PLC).
Changed settings become active immedi-
ately.
-
-
0
-
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:36
h
Modbus 17516
Profibus 17516
CIP 168.1.54
EthOptMapOut1 Optionally mapped output parameter 1 (PLC
to drive)
Modbus address of parameter which is
optionally mapped to Ethernet/IP assembly
or Modbus TCP I/O scanner data (PLC to
drive).
Changed settings become active immedi-
ately.
-
-
0
-
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:2E
h
Modbus 17500
Profibus 17500
CIP 168.1.46
EthOptMapOut2 Optionally mapped output parameter 2 (PLC
to drive)
Modbus address of parameter which is
optionally mapped to Ethernet/IP assembly
or Modbus TCP I/O scanner data (PLC to
drive).
Changed settings become active immedi-
ately.
-
-
0
-
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:2F
h
Modbus 17502
Profibus 17502
CIP 168.1.47
EthOptMapOut3 Optionally mapped output parameter 3 (PLC
to drive)
Modbus address of parameter which is
optionally mapped to Ethernet/IP assembly
or Modbus TCP I/O scanner data (PLC to
drive).
Changed settings become active immedi-
ately.
-
-
0
-
UINT16
UINT16
UINT16
UINT16
R/W
per.
-
CANopen 3044:30
h
Modbus 17504
Profibus 17504
CIP 168.1.48
5 Commissioning
LXM32M
48
Modbus-TCP module
0198441113843, V1.01, 01.2012