24-Pump, 128-Station Controller Chapter 6: Configurable Settings 69
6-3 Options for Pump Setup
Several of the items in this screen are not setup options but are instead intended for use
during operation. These items (hour meter and transferring stations to a standby pump) are
described in Chapter 4, “Operation.”
Name Description Options Default
Idle Time Options
Auto Shutdown Delay Length of time the pump continues to run
unloaded without demand from any station.
After this time has elapsed, the pump shuts
down to save power and to prevent wear on the
pump.
Adjust this setting to fit the needs of your facility
in trading off the savings against the costs
associated with waiting for a pump to start up
when there is a demand for material.
0–999 sec. 45 sec.
Alarm Options
Local alarm When this option is enabled, the controller turns
on the local alarm light for any alarm at this
specific pump.
Enable this option if and only if your facility has
installed a local alarm light for this pump.
disabled,
enabled
disabled
Pump fault #1 The ArmorBlock for each pump has two inputs
that you can wire to generate alarms for
situations of your choosing. These alarms can
be configured as standard or critical. Standard
means that the pump continues to operate.
Critical means that the pump is disabled.
For example, you may have a sensor that turns
on when material reaches the top of a filter-
chamber waste bin. When this option is
enabled, the controller issues an alarm if the
sensor wired to the input for Pump Fault #1
turns on.
Enable this option if and only if your facility has
installed a miscellaneous alarm on the input for
Pump Fault #1 for this pump.
disabled,
enabled
disabled
Pump fault #2 See the explanation for Pump fault #1 above.
Enable this option if and only if your facility has
installed a miscellaneous alarm on the input for
Pump Fault #2 for this pump.
disabled,
enabled
disabled
Filter Cleaning Options
Blow back When this option is enabled, the controller
periodically sends compressed air backward
through the pump’s air filter to dislodge
accumulated dust and debris.
Enable this option if and only if the pump has
the equipment for compressed air filter cleaning.
disabled,
enabled
disabled
Every n loads Number of conveying cycles to stations between
filter cleanings.
Adjust this setting based on experience. The
more dust and debris in your material line, the
smaller this number needs to be.
1–99 5