8 PARAMETER FUNCTIONS
8-27
8
APPENDIX 1 PARAMETER LIST (NUMERICAL ORDER)
Instruction
Code
Data
No. Name Setting Range
Initial
Value
Customer
Setting
read Write Extension
Refer
to
42 Speed detection 0 to 7200r/min 720 2A AA 0
43
Speed detection
for reverse
rotation
0 to 7200r/min,
9999
9999 2B AB 0
8-23
52
Main display
screen data
selection
Refer to manual
description.
0 34 B4 0 8-22
54
FM terminal
function selection
Refer to manual
description.
136B60
55
Speed
monitoring
reference
0 to 7200r/min 7200 37 B7 0
56
Current
monitoring
reference
0.00 to 500.00A
Rated
moter
current
38 B8 0
8-25
70
Regenerative
brake duty
0.0 to 15.0% 10 46 C6 0 8-9
73
Speed command
range selection
0, 1 0 49 C9 0
74
Filter time
constant
0 to 8 1 4A CA 0
8-3
75
Disconnected PU
detection/PU
stop selection
0 to 3 0 4B CB 0 8-2
77
Parameter write
disable selection
0, 1, 2 0 4D CD 0 8-1
78
Reverse rotation
prevention
selection
0, 1, 2 1 4E CE 0 8-7
84
Rated motor
speed
Read-only 54
08-10
117 Station number 0 to 31 0 11 91 1
118
Communication
speed
48, 96, 192 192 12 92 1
119
Stop bit
length/data length
0, 1, 10, 11 1 13 93 1
120
Parity check
presence
/absence
0, 1, 2 2 14 94 1
8-11