Mitsubishi Electronics MD-CX522-04K to s.7K Building Set User Manual


 
8 PARAMETER FUNCTIONS
8-1
8
8. PARAMETER FUNCTIONS
Refer to Appendix 1 for the parameter list.
MEMO
The minimum increment of the setting is 0.1 in the setting range 0.0 to
60.0, or 1 in the range 0 to 60.
The value having a 0 on the right of the decimal point can be
entered as an integer. (Example: 10.0
10)
If any parameter cannot be set, check that:
The start signal (STF or STR) is not "ON".
The parameter write disable selection (Pr. 77) setting has not been
made.
The PU operation mode has not been selected.
When the PU operation mode cannot be selected, check that:
The start signal (STF or STR) is not "ON".
8.1 Protection and Editing of the Parameters
Pr. 77 "parameter write disable selection"
You can select between write-enable and disable for parameter setting.
Setting Function Exceptional Parameters
0
You can change the setting only
during a stop in the PU
operation mode.
Even during operation, you can change the
values of the parameters whose numbers are
shaded in the parameter list in Appendix 1.
1
Whether the motor is running or
at a stop, you cannot change
the settings in any operation
mode.
Parameter clear, parameter all
clear operations are also
disabled.
Pr. 22 [Section 8.5.4], Pr. 75 [Section 8.2], and
Pr. 77, Pr. 188 [Section 8.4] allow their values
to be changed in any operation mode.
2
Whether the motor is running or
at a stop, you can change the
values in any operation mode.
Pr. 189 [Section 8.4], and Pr. 190, Pr.194
[Section 8.7.2] allow their values to be changed
during a stop only.