8 PARAMETER FUNCTIONS
8-25
8
8.7.5 Selection of the instrument connection terminal functions
Pr. 54 "FM terminal function selection"
You can select the signals output to the FM terminal designed for instrument
connection.
Setting Display Data Unit Full-Scale
1 Motor speed r/min Value set in Pr. 55
2 Motor current A Value set in Pr. 56
5 Preset speed r/min Value set in Pr. 55
MEMO
The maximum number of pulses of the terminal FM is 2400
pulses/s.
The output signals from the terminal FM is updated at intervals of
several 10ms.
Pr. 55 "speed monitoring reference"
Pr. 56 "current monitoring reference"
The terminal FM outputs a 1440 pulse/s signal at the value set in Pr. 55 or 56.
Pr. Setting Range Unit
55 0 to 7200 r/min
56 0.00 to 500.00 A
1440 pulses/s(terminal FM)
Selection signal Pr.55
Pr.56
Output or
indication
Pr. 900 "FM terminal calibration"
Using the parameter unit, you can calibrate the full scale of a meter connected to
the FM instrument connection terminal.
The terminal FM outputs a 1mADC current at the value set in Pr. 55 or 56. When
the full scale of the meter used must be calibrated, it can be adjusted using Pr.
900.
For the calibration procedure, refer to the instruction manual of the parameter
unit.