8 PARAMETER FUNCTIONS
8-23
8
8.7.2 Selection of the control circuit output terminal functions
Pr. 190 "RUN terminal function selection"
Pr. 194 "FU terminal function selection"
You can select/change the functions of the control circuit output terminals. At the
initial values, the terminal names and signal names match.
Setting
Signal
Name
Operation
0RUN
"ON" during motor operation, "OFF" during voltage braking
operation or stop.
3OL
Turns "ON" when overload is Pr. 22 setting or higher.
Refer to: 8.5.4 Stall prevention operation level
4FU
Turns "ON" at the preset speed or more.
Refer to: 8.7.3 Detection of running speed
12 Y12
"ON" at the preset output current or higher.
Refer to: 8.7.4 Detection of output current
21 UVT
Turns "ON" when AC input power supply voltage is
insufficient.
Refer to: 6.1.1 Protective function
acticvated (Undervoltage)
25 FAN Turns "ON" only when the cooling fan fails.
98 LF
Turns "ON" at a fan failure or communication error alarm.
Refer to: 8.5.5 Other settings
Refer to: 8.6 Communication operation from
the PU connector
99 ABC
Turns "ON" when the protective function is activated.
Refer to: Chapter 6 Troubleshooting
9999
No function
8.7.3 Detection of running speed
Pr. 42 "speed detection"
Pr. 43 "speed detection for reverse rotation"
Pr. Setting Range Unit Signal
42 0 to 7200 r/min FU
0 to 7200 r/min FU
43
9999
