Commander GP User Guide
Issue code: gpxu2
Setting Up the Drive 3-21
3.6 Macro 3
Preset frequencies
Features
Special features
Selection can be made between preset frequencies
and analog frequency control. In both cases, analog
input 1 remains configured for an analog frequency
reference signal (0 to 10V).
Up to four preset frequencies can be used; their
values must be programmed into individual
parameters. Selection is made by external contacts
operating in binary logic.
Standard features
Macro 3 operates in Terminal mode only
Digital control by RUN FORWARD and
RUN REVERSE contacts
Analog frequency input
Adjustment of minimum and maximum
frequencies
Adjustment of acceleration and deceleration
ramps
Operation of the status relay can
be inverted
S-ramp
Skip frequencies
Selection of stopping modes
Selection of braking mode
Motor thermistor input
Negative logic for the digital inputs
SPEED and TORQUE analog outputs
External trip digital input
Drive RESET digital input
Signal connections for Macro 3
0V common
Analog frequency
reference 1
(remote) 0 ~ 10V
SPEED
TORQUE
0V common
PRESET SELECT
A
RESET
PRESET SELECT
B
RUN FORWARD
External trip
0V common
ANALOG I/P
PRESET REFS.
Status relay
Drive healthy
RUN REVERSE
PRESET ENABLE
Motor thermistor
Signal
connector
Figure 3–8 Control signal and thermistor
connections for Macro 3
For electrical specifications, refer to Appendix C
Signal Connections.