HP (Hewlett-Packard) c7000 Doll User Manual


 
HP BladeSystem Insight Display 67
o
None
Limit AC Input VA—The default setting is Not Set. You can change the Max AC Watts in increments of
50 Watts.
Power Savings—The default setting is Enabled. The following selections are valid:
o EnabledYou can place some of the power supplies on standby automatically to increase overall
enclosure power subsystem efficiency.
o DisabledAll power supplies share the load; the power subsystem efficiency varies based on load.
OA1 IP Addr—The default setting is DHCP. If no IP address is received, the IP address is 0.0.0.0. The
IP address, mask, and gateway are set within this option.
OA2 IP Addr—If this module is present, the default setting is DHCP. If no IP address is received, the IP
address is 0.0.0.0. If only one Onboard Administrator module is installed, the screen will display Not
Present.
Enclosure NameThe default setting is a unique factory-assigned name. The accepted character values
are 0–9, A–Z, a–z, -, _ and . is used to signal the end of the name.
NOTE: Do not use the symbol in the middle of a text field. Entries in text fields will be
truncated to the last character before the symbol.
TIP: Select Clear from the navigation bar to quickly clear entries in text fields up to the
symbol.
Rack Name—The default setting is UnnamedRack The accepted character values are 09, AZ, az, -,
_ and . is used to signal the end of the name.
Insight Display PIN#—The default setting is Not Set. HP recommends that you set a PIN to protect the
enclosure configuration from unauthorized changes. You must enter the PIN after each inactivity period
to change options in the Enclosure Settings menu. The accepted character values are 09, AZ, az, -,
_ and . is used to signal the end of the name.
5. Navigate to the Accept All button at the bottom of the Enclosure Settings screen, and press the OK button
to accept all the settings and continue.
6. In the Check: Linked Enclosures screen, the message Linked enclosures detected appears if the
Onboard Administrator module detects other enclosures. Use the up and down arrow buttons to change
Push Settings = to one of the following values: