Page 60 of 86 SSC Series Central Chilling Stations
Compressor Hourmeters” contains the lifetime and resettable
hour meters to show the number of hours that the compressors
have been running
If the chiller was configured to operate the chilled water pump
tank, there are three screens to configure and view the pump
tank setup. The configuration screen allows for the user to turn
on or off any of the pumps as well as configuring the lead/lag
rotation (if multiple pumps were configured)
Chiller Configuration” shows the configuration of the chiller
itself including the chiller temperature setpoint, temperature
alarm settings, as well as setting up the lead/lag rotation, and
the ability to turn on and off the compressors.
PanelView Utilities” and “ACS Service” are both password
protected sections of the PLC that are used to configure the
display and the initial configuration of the chiller and system.
The following sections in this chapter list the information you need
to navigate through these screens for operating and monitoring
your SSC Series central chilling station with the Standard Control
Package.
8-4 Viewing and Operating Chiller Compressors
Viewing Compressor Status
To view the status of the chiller compressors, start at the Main
Menu screen, then:
n Press the Up or Down buttons on the right side of the screen to
highlight “System Information
n Press
The chiller status screen displays: