! DANGER
Improper electrical connections
can damage the unit and cause
serious operator injury or death!
Bring properly sized power leads and ground from a fused
disconnect (installed by your electrician) to the unit. Provide
external overcurrent protection to the unit, using circuit breakers or
fuses. If you use fuses, make sure that they are dual-element time-
delay fuses, sized according to your electrical code. Make sure that
all electrical connections are tight.
Important!
1. Electrical connections must comply with all applicable electrical codes.
2. The chiller must be grounded in accordance with NEC Article 250.
3. Voltage must be within plus or minus ten percent (±10%) of the nameplate
rating.
4. Make sure your installer provides external protection.
Check the electrical wiring schematic
provided in your Customer Information packet
for additional information.