Page 50 of 86 SSC Series Central Chilling Stations
7-5 Viewing and Operating Chiller Pumps
If your chiller system was configured to operate the pump(s) of the
chilled water pump tank the user may view the status of the
process and recirculation pumps.
Viewing Chiller Pump Status
To view the status of the pumps, start from the Main Menu, then:
n Press the or buttons to highlight either “PROC
PUMP STATUS”or “RECIRC PUMP STATUS”.
n Press
The Pump Status Screen appears
Pump Status Screen
Only pumps that are included in the system will be shown on this
screen. Pumps will display one of the following states:
1. OFFLINE This indicates that the pump has been turned off in
the pump enable/disable screen. The pump will not be called
to operate until it has been re-enabled.
2. READY Indicates that the pump is enabled and ready to run.
However, the current number of pumps specified to run does
not require this pump to operate.
3. RUNNING Pump is currently running.
4. FAULT A safety on the pump indicates a fault condition and
the pump has been deactivated. Once the problem is remedied,
the pump will return to a READY state unless it is put in the
OFFLINE state.