SSC Series Central Chilling Stations Page 25 of 86
SSC Series condensing pressure
with 95ºF (35ºC) condenser air
R-22 = 260 psi (1,793 kPa/17.93 bars)
Note: Due to the variables involved in remote air-cooled condenser installations, no set or
standard piping procedure exists. Each installation must be designed and installed by
qualified persons. Follow the instructions supplied with the condenser.
3-11 Checking Motor Direction
Compressor
Note:
Never switch contactor leads or motor leads for reversing
rotation.
Do not use contactor or motor leads for phase matching.
Compressor noise from reverse rotation is noticeable. Do not
run in this mode for more than ten (10) seconds. The
compressor shuts off if run longer in this mode.
Reverse rotation can cause suction and discharge pressures to
be approximately equal; amp draws will be lower than normal.
If you discover that compressor rotation is reversed, correct it
by switching any two main power leads into the disconnect
switch or distribution block on the unit.
Water Pump
A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07
bars) on the TO PROCESS line indicates correct pump rotation.
Condenser Fan
On SSC Series remote air-cooled units, air should draw through
the condenser and discharge up from the condenser.
Changing fan rotation direction
Disconnect and lock out power at the fused disconnect.
If all fans are going backwards, reverse any two main power
leads.
If only some of the fans are going backwards, switch any two of
their respective motor leads.