GE FVR-C9S-2UX Drive Series Model Vehicle User Manual


 
31
FVR-C9S-2UX
F 1 7 Data Initialization
Reset the data for all of the functions to the value set at the factory.
0
Inactive
1
Resets to the value set at the factory.
From the _ _ 0 display, by simultaneously pressing STOP and UP, the display will change to _ _ 1.
By pressing FUNC/DATA in this state, the data will be reset to the value set at the factory, and the mode
will automatically change to the 6 0. 0 frequency display mode.
F 1 8 Retry
The number of times of retry for automatic restart after the drive has been tripped can be set.
0
The number of retry times is fixed at 5. Retry takes place in 0.5s after trip
1
Note that the retry takes place only in the case where the drive is tripped due to overcurrent or
overvoltage applied during operation.
F 1 9 Motor Characteristics
Used to compensate for output current instability.
F 2 0 Jump Frequency Range
F 2 1 Jump Frequency 1
F 2 2 Jump Frequency 2
F 2 3 Jump Frequency 3
Frequency is jumped so that the mechanical common point of load and the output frequency of drive do not
coincide with each other.
Jump frequency 1
Jump frequency 2
Jump frequency 3
50X
50X
Jump
Width
Output
frequency
Set frequency
Jump width is changeable within
0-10 Hz range in a unit of 1 Hz.