Function Code Tables
Function
Code
Function Date Code Range Unit
Min.
Set.
Factory
Setting
Change
During
Operation
F15
Motor Running
Sound
0 - 5 (code) 5 Yes
F16 Fault Memory
The current and previous 3 fault events are displayed
in order of occurrence
—— No
F17 Data Initialization
0: Inactive
1: Reset to the initial value (value set at factory)
—— 0 No
F18 Retry
0: Inactive
1: Active (Retry times fixed at 5, Retry starts in
.05s after trip)
—— 0 No
F19
Motor
Characteristics
0 - 10 4 Yes
F20
Jump Frequency
Range
0 - 10Hz Hz 1 3 Yes
F21 Jump Frequency 1 0 - 120Hz Hz 1 0 Yes
F22 Jump Frequency 2 0 - 120 Hz Hz 1 0 Yes
F23 Jump Frequency 3 0 - 120 Hz Hz 1 0 Yes
F24 High Limiter 0 - 100% % 1 100 Yes
F25 Low Limiter 0 - 100% % 1 0 Yes
F26 Bias Setting 0 - 100% % 1 0 Yes
F27
THR Terminal
Function
0: External alarm input
1: Multistep speed selection (X1)
—— 0 No
F28
BX Terminal
Function
0: Motor coast-to-stop command input
1: Multistep speed selection (X2)
—— 0 No
F29
Multistep Speed
Setting 1
0.0 - 120 Hz Hz 1* 10.0 Hz Yes
F30
Multistep Speed
Setting 2
0.0 - 120 Hz Hz 1* 20.0 Hz Yes
F31
Multistep Speed
Setting 3
0.0 - 120 Hz Hz 1* 30.0 Hz Yes
F32 Meter Adjustment
0 - 99 (Full scale DC 6.5 - 10.5V)
1 85 Yes
F33
Meter Output
selection
0: Output frequency monitor
1: Output current monitor
1 0 Yes
*1 Frequency can be set in increments of 0.1 Hz within a range of 0.0 to 99.9 Hz, and can be set in increments of 1 Hz
C92-02