ELECTRICAL DATA
UNIT SIZE V/PH
OPER VOLTS* COMPR FAN
MCA
MIN WIRE
SIZE{
60° C
MIN WIRE
SIZE{
75° C
MAX
LENGTH
ft. (m)}
60° C
MAX
LENGTH
ft. (m)}
75° C
MAX FUSE**
or CKT BRK
AMPS
MAX MIN LRA RLA FLA
018---B
208/230/1---60 253 197
48.0 9.0 0.50 11.8 14 14 67 (20.4) 64 (19.5) 20
024---A 58.3 13.5 0.75 17.7 14 14 46 (14.0) 43 (13..1) 25
030---A 64.0 12.8 0.75 16.8 14 14 44 (13.4) 41 (12.5) 25
036---A 77.0 14.1 0.50 18.1 12 12 57 (17.4) 54 (16.5) 30
042---A 112.0 17.9 1.20 23.6 10 10 85 (25.9) 81 (24.7) 40
048---B 109.0 19.9 1.20 26.1 10 10 70 (21.3) 67 (20.4) 40
049---A 117.0 21.8 1.20 26.1 10 10 70 (21.3) 67 (20.4) 40
060---A 135.0 21.4 1.20 28.0 8 10 91 (27.7) 56 (17.1) 40
061---A 134.0 25.0 1.20 32.5 8 10 94 (28.7) 58 (17.7) 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). Th e ampacity of non---metallic--- sheath ed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC ( NFPA 70) Article 334---80. If other than un coated (no---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24--- V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Stan dar ds 90.1
A--WEIGHTED SOUND POWER LEVEL (dBA)
Un it Si ze ---
Voltage, Series
Standard
Rating (dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
125 250 500 1000 2000 4000 8000
0018---B 76 52.5 59.0 65.5 70.5 64.5 59.0 54.5
0024---A 76 57.5 64.0 69.0 71.0 69.0 64.5 60.0
0030---A 76 55.0 63.5 68.0 69.5 67.0 63.5 58.5
0036---A 76 50.5 59.5 64.5 70.5 62.0 59.5 54.5
0042---A 78 52.5 62.0 66.0 73.5 68.0 62.0 55.5
0048---B 78 57.5 61.5 66.0 70.5 65.5 59.5 53.5
0049---A 78 51.5 62.0 67.5 73.5 69.0 64.5 62.0
0060---A 78 55.0 62.5 67.5 70.5 65.0 61.0 53.5
0061---A 78 56.5 63.0 65.5 69.0 67.0 61.5 56.0
NOTE: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).
A--WEIGHTED SOUND POWER LEVEL (dBA) WITH SOUND SHIELD
Un it Si ze ---
Voltage, Series
Standard
Rating (dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
125 250 500 1000 2000 4000 8000
0018---B 74 55.5 59.0 65.0 68.5 63.5 58.0 52.0
0024---A 75 58.0 64.0 69.0 70.5 68.5 64.5 59.5
0030---A 75 55.5 63.0 68.0 69.0 67.0 63.0 58.5
0036---A 74 51.5 58.5 62.0 65.0 61.0 58.0 52.0
0042---A 76 53.0 62.0 65.5 72.0 65.0 61.0 54.0
0048---B 76 58.5 61.5 66.0 69.0 64.0 58.5 51.0
0049---A 76 53.0 61.5 67.5 72.0 68.0 61.5 59.0
0060---A 75 56.5 62.5 66.5 68.0 63.0 59.5 51.5
0061---A 75 57.0 63.0 65.5 67.0 65.5 59.0 52.5
NOTE: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES REQUIRED SUBCOOLING _F(_C)
018---B 10 (5.6)
024---A 10 (5.6)
030---A 10 (5.6)
036---A 10 (5.6)
042---A 9 (5.0)
048---B 10 (5.6)
049---A 8 (4.4)
060---A 9 (5.0)
061---A 9 (5.0)
116B