3.9 Paralleling DS2100 Units through the D.C. Bus
DS2100 units can be paralleled via the D.C. Bus, in order to share regeneration power.
3.9.1 mA Size DC Bus Inter-connection
Tie screen to chassis via
EMC bracket. See Section 2
L1 L2 L3 PE
(J6.4)(J6.5)(J6.6) Stud
Connector J6
DC- DC+
(J6.1)(J6.2)
DS2100
A
L1 L2 L3 PE
(J6.4)(J6.5)(J6.6) Stud
DC- DC+
(J6.1) (J6.2)
DS2100
A
a.c. Mains
L1
L2
L3
Protective
Earth
Connector J6
Figure 3.21 Size mA DC Bus Inter-connection
- Fixed connector: 12 pins, male connector
- Mating connector, 12 pins, female, supplied with the drive. Phoenix Combicon (Part # GMSTB 2.5/12-ST-7.62)
- mA size wiring: cable 14 AWG (2.1 mm
2
). Wire stripping: 7 mm.
- PE Stud wiring: cable 6 AWG (13mm
2
)
- Tightening torque: 0.5Nm.
To comply with the EMC Directive, the DC Bus cable must be
shielded and the shield must be connected to the housing with a 360
o
connection at both ends.
Required for
CE-Compliance
CAUTION – To connect drives through the DC bus, please contact
Moog application engineering for advice.