Dometic EIR600d Doll User Manual


 
OPERATION Eskimo Ice Installation Manual - Remote System
12 L-2448B ENGLISH
Figure 7: Control Panel
SYSTEM SHUTDOWN
Temporary Shutdown - Some system conditions result in a temporary shutdown followed by an automatic restart once the
situation is resolved. This is normal behavior, for example when the ice-level sensor detects that the ice bin is full.
Sustained Shutdown - Some system failures result in a sustained shutdown and are indicated by the appropriate fault code
flashing in the digital display. A reset indicates an actual problem, not just a passing event, and the cause should be
investigated.
Sustained shutdown in need of reset is caused by any of these events:
High-pressure switch triggered 3 times within 30 minutes.
Low-pressure switch triggered 3 times within 30 minutes.
Ice-clog switch on ice-discharge nozzle triggered 3 times within 30 minutes.
Auger motor high amps and low amps each time the fault occurs.
Compressor high amps and low amps each time the fault occurs.
NOTE: If system needs to be reset more than twice within one day, have the system serviced.
SYSTEM RESTART/RESET
Use any of these methods to restart operation:
Turn the unit off then on at either the main digital control box or the optional remote digital display.
Press the Reset switch on the unit’s control panel.
Turn the unit’s circuit breaker off then on.
Table 1: Digital Control - Diagram Legend
1
Digital display
7
Power indicator
2
Ice Bin Full indicator
8
Low Pressure fault light
3
Function button
9
High Pressure fault light
4
Auger indicator
10
Water Flow fault light (for freshwater feed)
5
Power button (on/off)
11
Ice Flow fault light (for clogs)
6
Compressor indicator
1
2
3456
7
8
9
10
11