A SERVICE OF

logo

Regency
®
E33S-1 Sunrise Gas Insert 7
INSTALLATION
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The FPI Gas Insert must be installed in accord-
ance with these instructions. Carefully read all
the instructions in this manual rst. Consult
the building authority having jurisdiction to
determine the need for a permit prior to starting
the installation.
NOTE: Failure to follow the instructions could
cause a malfunction of the heater which could
result in death, serious bodily injury, and/or
property damage. Failure to follow these
instructions may also void your re insurance
and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combustion.
Always provide adequate combustion and
ventilation air. Follow instructions and
information in CSA B149.1 (in Canada) or the
National Fuel Gas Code ANS Z223.1/NFPA
(in the USA), regarding requirements for
combustion and ventilation air.
GAS PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than
1/2 psig. (3.45 kPa).
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit
must be disconnected.
Gas Input Capacity:
Natural Gas 26,000 Btu/h
Propane 23,000 Btu/h
Min. Input:
Natural Gas 13,500 Btu/h
Propane 12,000 Btu/h
Fuels: Approved for use with both natural gas,
and propane. Approved as is for use at 0' to
4,500' (0-1370m).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 127 CFM.
Vent System: 3" co-linear aluminum ex.
Cobalt Blue Glass Crystals
INSTALLATION INTO A
SOLID FUEL BURNING
FIREPLACE OR
FACTORY BUILT
FIREPLACE
The E33S Gas Insert have been tested and
approved to be vented into any masonry
fireplace or approved solid fuel burning
factory built replace that will allow the insert
to physically t into the rebox. Refer to the
"Minimum Fireplace Dimensions" section.
If the factory built replace* height is too low
for your Insert, you may remove the smoke
baf e plate and damper from the factory
built replace as long as these items are
saved and are reinstalled in the event that
the Insert is removed. NOTE: Any alterations
made to the listed solid fuel burning factory
built replace may void the listing of the
replace. Cutting any sheet-metal parts of
the replace, in which the gas replace insert
is to be installed, is prohibited.
If the factory-built replace has no gas
access hole(s) provided, an access hole of
1.5" (37.5mm) or less may be drilled through
the lower sides or bottom of the rebox in
a proper workmanship like manner. This
access hole must be plugged with non-
combustible insulation after the gas supply
line has been installed.
The replace and replace chimney must
be clean and in good working order and
constructed of non-combustible materials
and chimney cleanouts must t properly.
Refractory, glass doors, screen rails, screen
mesh, and log grates can be removed
from the replace before installing the gas
replace insert. Smoke shelves, shields
and baf es may be removed if attached by
mechanical fasteners. A tight connection
between the gas replace insert ue collar
and the replace chimney must be made.
*Check with your local inspector before
commencing with this installation.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
General Safety Information
1) The appliance installation must conform
with local codes or in the absence of local
codes, with CAN/CSA B149.1 (in Canada)
or the National Fuel Gas Code ANSI Z223.1
NFPA 54 in the U.S.A. This appliance should
be installed by a quali ed gas tter technician
only.
2) Installation and repair should be done
by a quali ed service person.
3) The appliance should be inspected
before use and at least annually by
a professional service person. More
frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, animal hair, etc. It is imperative
that control compartments, burners
and circulating air passageways of the
appliance be kept clean.
4) See general construction and assembly
instructions. This appliance may only be
installed in a vented, noncombustible
replace.
5) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) Always connect this appliance to a vent
system vent that is run (or routed) to the
outside of the building envelope. Never vent
to another room or inside a building. Make
sure that the vent is properly sized and is
of adequate height to provide the proper
draft.
7) Inspect the venting system annually for
blockage and any signs of deterioration.
8) Any glass removed for servicing must be
replaced prior to operating the appliance.
9) WARNING: Failure to position the parts
in accordance with the diagrams in
this manual or failure to use only parts
speci cally approved with this appliance
may result in property damage or
personal injury.
10) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
replace.
Installer must mechanically attach the supplied
label to the inside of the rebox of the replace
into which the gas replace insert is installed.
"WARNING: This replace has been converted
for use with a gas replace insert only and
cannot be used for burning wood or solid fuels
unless all original parts have been replaced,
and the replace re-approved by the authority
having jurisdiction."