INVERTER OPERATION DIP SWITCH
SETTINGS
(SUIOKPM
SHOWN)
Using a small tool, set the four Inverter Opera-
tion DIP Switches (located on the rear panel of
your UPS, see pg.
4-5
for location) to match
your input voltage, input frequency and
desired operational mode.
InDut Voltage Selection
(D~P
switch&
#
1
~r
#2)
(Input Voltage Select Terminal Block)
These DIP switches and the Input
Terminal
Select Block must BOTH be set to match your
input voltage. Your UPS WILL
NOT
CONVERT
the voltage.
Input Voltage
Jn~ut Volt= DIP Switch Position Select Terminal Block
240V
#1
DOWN
&
#2 DOWN
Invut Frequencv Selection
(DIP Switch
#3)
Your Input Frequency setting MUST match your input frequency. Your UPS WILL NOT
CONVERT the frequency.
Input Frequency DIP Switch Position
60
Hz
#3
DOWN
Overational Mode Selection
(DIP Switch
#4)
The "On-Line" Mode provides on-line operation with zero transfer time. The "Economy"
Mode provides line-interactive operation for increased efficiency when on-line protection
is unnecessary, thus reducing operating costs without affecting your
UPS'S output
reliability during
a
power outage.
Input Frequency DIP Switch Position
On-Line
#4
UP
Economy
#4 DOWN