24
Operation
8
The EXTERNAL BATTERY TYPE selection screen will appear.
EXTERNALBATTERYTYPEreferstotheabilityfortheUPStobecomeawareofwhichexternal
battery pack is connected to the UPS. Setting the external battery configuration enhances
the accuracy of the MINUTES RUNTIME countdown during power failure conditions. The LCD
interface supports no external batteries with the factory configuration of BP0. Two additonal
LCD configurable external battery pack options are available under the user selection of BP0,
BP1&BP2.SeethetabletodeterminewhetherBP1orBP2appliestoyourexternalbattery
pack. If your battery pack is not listed or you are using more than one of any supported
externalbatterypack,youmustuseTrippLite’sEXTERNALBATTERYCONFIGURATIONTOOL
softwareavailablefordownloadatthislink:http://www.tripplite.com/bpconfig
NOTE: Use the BP0 setting if you plan to use the EXTERNAL BATTERY CONFIGURATION TOOL
software. After the software configuration is run, the UPS LCD screen will report “BPC”.
The UPS can be reset from BPC to BP0, BP1 or BP2 settings via the LCD screen, but once
the new configuration is set, you’ll need to run EXTERNAL BATTERY CONFIGURATION TOOL
software again to re-configure back to the unique BPC setting.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
BP0 (factory), BP1, BP2
(BPC reflects a software set
configuration)
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).
UPS MODEL BP0 BP1 BP2 ALL OTHER BATTERY PACK CONFIGURATIONS
SU1000XLCD
No BP Qty1BP24V15RT2U Qty1BP24V28-2U UseEXTERNALBATTERYCONFIGURATIONTOOLsoftware
SU1500XLCD
No BP Qty1BP48V24-2U Qty1BP48V60RT3U UseEXTERNALBATTERYCONFIGURATIONTOOLsoftware
SU2200XLCD
No BP Qty1BP48V24-2U Qty1BP48V60RT3U UseEXTERNALBATTERYCONFIGURATIONTOOLsoftware
SU3000XLCD
No BP Qty1BP72V15-2U Qty1BP72V28RT3U UseEXTERNALBATTERYCONFIGURATIONTOOLsoftware
9
The VIEW IP ADDRESS selection screen will appear.
TheVIEWIPADDRESSisadisplayfieldthatenablesviewingofthecurrentUPSIPaddresswhen
the SNMPWEBCARD option is in use. The UPS is only capable of displaying a IPv4 level IP address
whenconfiguredwiththeSNMPWEBCARD.IfVIEWIPADDRESSisattemptedforIPv6levelIP
address or for a UPS configuration without the SNMPWEBCARD, the LCD screen will report NA.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
ToADVANCEtobacktothe
OUTPUT VOLTAGE selection
screen, press the ON/SELECT
button (less than 1 second).
ToVIEWIPaddressinformation
in 3 digit segments, press the
SETUP button repeatedly (less
than 1 second).
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).