Output frequency
regulation
Frequency is regulated to 50/60Hz +/-0.05 Hz. Frequency conversion from 50 to 60Hz and 60 to 50Hz is supported
(output watt capacity is reduced by 25% in when frequency conversion is in use).
Outlet quantity /
type
7 outlets total (6 5-15/20R / 1 L5-30R)
Customized load
management
receptacles
Two individually controllable load banks (each bank consists of 3 5-15/20R outlets)
Overload
protection
L5-30R outlet is non breakered, load banks 1 & 2 (three 5-15/20R outlets each) are protected by separate 20A circuit
breakers
INPUT
Maximum input
amps
24A (120v)
Input connection
type
L5-30P (120V 30A)
Input cord length 10 ft / 3m
Recommended
Electrical Service
100/110/115/120/127V 30A
BATTERY
Full load runtime 6 minutes (2500w)
Half load runtime 15 minutes (1250w)
Expandable
battery runtime
Runtime is expandable with optional BP72V15-2U (limit 1) and BP72V28RT3U (multi-pack compatible) external battery
packs
DC system voltage 72VDC
Battery recharge
rate
6.8 hours to 90%
Replacement
Battery Cartridge
RBC96-2U
VOLTAGE REGULATION
Voltage regulation
description
In double conversion mode, output is regulated within 2% of selected nominal voltage. In economy mode, output is
regulated within -12% / +10% of selected nominal voltage.
Overvoltage
correction
Corrects overvoltages to 144V
Brownout
correction
Corrects undervoltages to 80V (70V at less than 70% load)
LEDS ALARMS & SWITCHES
Front panel LEDs LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery
low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%). LCD display panel easily rotates for
viewing in rackmount or tower configurations.
Alarms Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 seconds on / 0.5 seconds
off), low battery warning (1.25 seconds on / 0.5 seconds off), overload (sounds continuously), UPS fault (4.2 seconds on /
1 second off), input voltage out of frequency (2.1 seconds on / 0.14 seconds off) and high input voltage (2.1 seconds on
0.07 seconds off)
Switches Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal
AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch) - all switch functions
require that the switch be pressed and held for longer than 2 seconds, but less than 4 seconds
SURGE / NOISE SUPPRESSION
AC surge
suppression
504 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes