17
Operation
BYPASS MODE:
BYPASSisanoperatingmodewheretheUPSispassingunprocessed
input power directly through to the output. BYPASS MODE can
engage onanautomatic basis(AUTO-BYPASS)as anemergency
UPSoperatingmodethatmaintainsoutputtoconnectedequipment
in case of UPS overload or internal component failure that would
otherwisecauseconnectedequipmenttolosepower.AUTO-BYPASS
MODE operation resulting from sudden UPS overload as the UPS is
running in ON LINE MODE will automatically reset, once the output
loadisreduced.BYPASSMODEresultingfrominternalUPSfailure
may not automatically reset, and if the message persists, users
should contact Tripp Lite for troubleshooting or repair options.
Regardless of the cause, the UPS will not provide battery backup
anytimetheUPSisrunninginBYPASSMODE.
BYPASS MODE SAMPLE LCD SCREEN
LCD ELEMENTS CONFIRMING BYPASS MODE OPERATION
>INPUTICON:ONSOLID(inputpowerispresent,bypassisavailable)
>SINEWAVEPLUSDOTICON:ON(CONFIRMSBYPASSMODE)
BYPASS MODE LCD VIEWING OPTIONS:
WhentheUPSentersBYPASSMODE,theLCDscreenwillcontinue
reporting the last viewed informational screen (INPUT VOLTAGE
shown). To display additional information screens, tap the SETUP
button repeatedly. The 10 available information screens are (1)
INPUTVOLTAGE,(2)INPUTFREQUENCY,(3)OUTPUTVOLTAGE,(4)
OUTPUTFREQUENCY,(5)LOADPERCENTAGE,(6) LOADKVA,(7)
LOADKW,(8)BATTERYCHARGEPERCENT,(9)BATTERYVOLTAGE,
(10) ESTIMATED RUNTIME.
STANDBY MODE:
When first connected to a live power source, the UPS will
automatically energize in Standby mode and report OFF on the LCD
screen. The charger will activate as necessary, but there is no UPS
output or battery backup support available in this mode. To turn the
UPS on for normal operation, press and hold the ON button until a
beepisheard;theUPSwillenergizeafteraseriesofdiagnostictests
are completed. To turn the UPS completely off from standby mode,
justunplugtheUPSfromitspowersource;theUPSwillturnOFFand
the fan and LCD screen will turn off after approximately 30 seconds.
STANDBY MODE SAMPLE LCD SCREEN
LCD ELEMENTS CONFIRMING STANDBY MODE OPERATION
>3CHARACTERDISPLAY:OFF(CONFIRMSOUTPUTPOWERISOFF)
STANDBY MODE LCD VIEWING OPTIONS:
WhentheUPSentersSTANDBYMODE,theLCDscreenwillreport
OUTPUT OFF to confirm that output power is not available. To display
additional information screens, tap the SETUP button repeatedly. The
10availableinformationscreensare(1)INPUTVOLTAGE,(2)INPUT
FREQUENCY, (3) OUTPUT VOLTAGE, (4) OUTPUT FREQUENCY, (5)
LOAD PERCENTAGE, (6) LOAD KVA, (7) LOAD KW, (8) BATTERY
CHARGEPERCENT,(9)BATTERYVOLTAGE,(10)ESTIMATEDRUNTIME.
13-03-138 93-3168-EN.indd 17 3/28/2013 1:05:25 PM