A SERVICE OF

logo

Unit Dimensions
(HWD/in)
7.01 x 18 x 17.25
Unit Dimensions
(HWD/cm)
17.8 x 45.7 x 43.8
Material of
construction
Steel
Form factors
supported
Rack (4U)
Cooling method Fan
Battery Access Battery access door allows hot swap battery replacement without powering connected equipment off
ENVIRONMENTAL
Relative Humidity 0-95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Line mode BTU/hr.
(Max.)
199.8 BTU/Hr. (with 1900w continuous load)
Battery mode
BTU/hr. (Max.)
880.9 BTU/Hr. (with 1900w continuous load)
COMMUNICATIONS
Network monitoring
port
Includes USB and DB9 serial ports. Built-in DB9 port offers both enhanced RS-232 enabled monitoring data, plus
contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and
auto shutdown features of Windows and Mac OS X.
Software and
cabling included
Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Ships with 2
cables, 1-USB to USB & 1-DB9 to DB9
SNMP compatibility Yes, includes slot for optional SNMPWEBCARD accessory (#SNMPWEBCARD)
WatchDog
compatibility
Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot
of application / OS or hard power off/on reboot of connected equipment ideal for unattended kiosk applications
LINE / BATTERY TRANSFER
Transfer time from
line power to
battery mode
5.5 milliseconds
Low voltage transfer
to battery power
Switches to battery power as line voltage drops to 83V or less. Switches back to line power mode as line voltage
recovers to 87V or higher.
High voltage
transfer to battery
power
Switches to battery power as line voltage increases to 145V or higher. Switches back to line power mode as line voltage
recovers to 141V or lower.
SPECIAL FEATURES
EPO port Includes RJ11 EPO (emergency power off) port and interconnection cable
Cold Start Yes, inverter can be "cold started" to enable temporary AC output during a power failure
Appearance Attractive black rackmount housing, optional use 2U black front bezel included to enable black color appearance
BATTERY PACK ACCESSORY (optional)
Battery Pack
Accessory (optional)
Compatible with BP48V24-2U (limit 1), BP48V48RT4U (multi-pack compatible)
CERTIFICATIONS
Certifications Tested to UL1778 (USA), CSA (Canada), NOM (Mexico), Class A (EMI), RoHS
WARRANTY
Product Warranty
Period
2 year product warranty
Connected
Equipment Coverage
$250,000connected equipment insurance