Overvoltage
correction
Input voltages between 127 and 140V AC are reduced by 12%
Direct pass through Input voltages between 110 and 127V AC are passed through unchanged
Brownout correction Input voltages between 95 and 105V AC are boosted by 10%
Severe brownout
correction
Input voltages between 87 and 94V AC are boosted by 22%
LEDS ALARMS & SWITCHES
Front panel LEDs Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE
REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Alarms Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches Includes 2 front panel switches; one on/standby power switch and one dual function "alarm cancel" / "self test" button,
plus 1 rear panel system enable switch
SURGE / NOISE SUPPRESSION
AC surge
suppression
480 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 87
Shipping weight (kg) 39.5
Shipping
Dimensions (HWD/in)
22.25 x 12.75 x 16.5
Shipping
Dimensions
(HWD/cm)
57.2 x 32.4 x 42
Unit weight (lbs) 80
Unit weight (kg) 36.3
Unit Dimensions
(HWD/in)
17 x 9 x 12.5
Unit Dimensions
(HWD/cm)
41.9 x 22.9 x 31.1
Material of
construction
Polycarbonate
Form factors
supported
Tower
Cooling method Convection
Receptacle Color BLACK
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit, -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit, 0 to +40 degrees Celsius
Battery mode
BTU/hr. (Max.)
502.6
COMMUNICATIONS
Network monitoring
port
Includes 3 built-in DB9 monitoring ports, 1 enabled with RS-232 data communications and 2 with standard contact
closure communications. All interfaces support on battery, low battery and power restored messaging. RS-232 enabled
port adds data regarding AC