SCH1 Scale High: Select 100 to 9999 counts above
SCL1SCL1
SCL1SCL1
SCL1. The total
span between
SCL1SCL1
SCL1SCL1
SCL1 and
SCH1SCH1
SCH1SCH1
SCH1 must be within 11998 counts.
Maximum setting range is -1999 to +9999 counts. Minimum
span is 100 counts. For Current and Voltage inputs, this will
set the high range end. Viewable only for Thermocouple and
RTD ranges.
SPL1SPL1
SPL1SPL1
SPL1 Set Point Low: Select from the lowest input range value to
SPH1 value. This will set the minimum SP1 value that can
be entered. The value for SP1 will not stop moving when this
value is reached. Attempting to set a value for SP1 lower
than SPL1 will result in a CHEC SP1 error. The value will not
be accepted.
SPH1SPH1
SPH1SPH1
SPH1 Set Point High: Select from the highest input range value to
SPL1 value. This will set the maximum SP1 value that can
be entered. The value for SP1 will not stop moving when this
value is reached. Attempting to set a value for SP1 higher
than SPH1 will result in a CHEC SP1 error. The value will not
be accepted.
S1StS1St
S1StS1St
S1St Set Point State: Select
dirdir
dirdir
dir or
rErE
rErE
rE.
dirdir
dirdir
dir Direct Action. As the input increases the output
will increase. Most commonly used in cooling
processes.
rErE
rErE
rE Reverse Action. As the input increases the output
will decrease. Most commonly used in heating
processes.
If
Out1Out1
Out1Out1
Out1 is set for ##
tPtP
tPtP
tP, #
PULPUL
PULPUL
PUL, or ProP, then S1OL and S1OH
(following) appear. If
Out1Out1
Out1Out1
Out1 is set for
ONOFONOF
ONOFONOF
ONOF, then skip to
S1rES1rE
S1rES1rE
S1rE.
S1OLS1OL
S1OLS1OL
S1OL Set Point Output Low Limit: Select
00
00
0 to
9090
9090
90% but not greater
than
S1OHS1OH
S1OHS1OH
S1OH. This item limits the lowest output value. This is
useful for adding a bias to the process when needed.
Factory set to
00
00
0 for output codes 1,2, 3, and 8. Factory set
to
2020
2020
20 for output code 5 (20% output equals 4 mA output).
S1OHS1OH
S1OHS1OH
S1OH Set Point Output High Limit: Select
1010
1010
10 to
100100
100100
100% but not less
than
S1OLS1OL
S1OLS1OL
S1OL for output codes 1, 2, 3, or 8. Select
1010
1010
10 to
102102
102102
102%
but not less than S1OL for output code 5. This item allows
setting the maximum output limit. This is useful with pro-
cesses that are over powered. Adjustment to 102% allows
setting current output to force a full on condition for output