SETTINGS AND PROCEDURE TO OPERATION
4.6 Self-diagnostics Test
4.6.2 Hardware test
4
- 13
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETTINGS AND
PROCEDURE TO
OPERATION
5
INSTALLATION AND
UNINSTALLATION
6
FUNCTIONS
7
MES INTERFACE
FUNCTION
CONFIGURATION TOOL
8
DB CONNECTION
SERVICE AND
SETTING TOOL
4.6.2 Hardware test
Test ROM/RAM/intelligent function module switch settings for the MES interface module.
(1) MES interface module operation mode setting
1 In [Switch setting for I/O and intelligent function module] of GX Developer, set
"Mode setting" to "Hardware test". (Switch 1: 0001h)
2 Match the other intelligent function module switch settings to the setting contents
used.
(2) Hardware test execution
1 Set the programmable controller CPU to STOP status.
2 Reset the programmable controller CPU.
3 After the programmable controller CPU is reset, the following hardware tests are
executed automatically.
During the test, the ERR. LED flashes.
1) ROM check
Reads the ROM data and checks the sum.
2) RAM check
Reads the test data written to the RAM and checks the consistency.
3) Switch setting check
Checks that the intelligent function module switch settings are set within the
allowable range.
However, the Switch 1 "Mode setting" is not tested.
(3) Confirmation of hardware test result
1 Check the ERR. LED status to see the hardware test result.
2 When the test is completed normally, set the "Mode setting" to "Online" with
[Switch setting for I/O and intelligent function module] of GX Developer and reset
the programmable controller CPU. (Switch 1: 0000h)
3 When the test has failed, check that the switch setting is correctly set, and
conduct the hardware test again.
If an error occurs again, a possible cause is the hardware failure of the MES
interface module.
Please consult your local Mitsubishi representative.
Table 4.8 Hardware test result
ERR. LED status Hardware test result
OFF Completed
ON Failed