1.Specification
1-1.Object Model
These specifications apply to the communication interface used to connect the LonWorks network and the Mitsubishi
Electric M-NET compatible products.
<Model name>
1. Multiple split type air conditioners CITY MULTI
2. Split-type air conditioners Mr.SLIM
NOTE:A-M Converter(PAC-SF48MA-E) is necessary.
3. Heat recovery ventilators LOSSNAY
NOTE:LOSSNAY Adapter(PZ-53ADF-E) is necessary.
1-2.Explanation of Function Setting
This product requires a function setting switch because of the connected model, system configuration and control functions.
SW NO. switch name Function Note
Factory
setting
Set timing
SW1-1
Function switch of local prohibit ON local prohibit effective
Operation local prohibit NV input from
L
ONWORKS becomes Effective when switch ON
OFF
Before turning on
the power suppl
OFF local prohibit ineffective
Operation local prohibit NV input fro
LONWORKS becomes invalid when switch OFF
SW1-2
Used together with MELAN
switch
ON used together with MELANS *4 OFF
Before turning o
the
ower su
l
*2 OFF
not used together with MELAN
*5
SW1-3
Indoor temperature stat
interval switc
ON
Transmission interva
1minutes or more
*The number of indoor units connected should b
30 or less *6
OFF
Before turning o
the
ower su
l
OFF
Transmission interva
10 minutes or more
SW1-4
Reset Filtersign/Select
enable/disable operation duration
ON
effective
When "ON",the reset filter sign input and the
operation duration output are enabled.
OFF
Before turning on
the power supply
OFF ineffective
When "OFF",the reset filter sign input and th
o
eration duration out
ut are disabled
SW1-5
Function switch of LOSSNAY ON
LOSSNAY is operate
from LONWORKS.
Please turn on the switch when LOSSNA
is o
erated from LONWORKS.
OFF
Before turning o
the
ower su
l
*3 OFF
LOSSNAY interlock
with indoor unit
Please turn off the switch when LOSSNA
interlocks with indoor units
SW1-7
Function switch of SNVT_switch ON SNVT standard
When "ON",the specifications of the NV using the
SNVT_switch comply with the SNVT Standards.
OFF
Before turning on
the power supply
OFF original
When "OFF",the NV using the SNVT_switch ha
ori
inal s
ecifications
SW1-8
Select enable/disable force
thermostat OFF
ON effective
When "ON",the forced thermo OFF NV input/outpu
are enabled
OFF
Before turning o
the
ower su
l
OFF ineffective
When "OFF",the forced thermo OFF N
in
ut/out
ut are disabled
SW1-9
Indoor units test run switch ON
ON (test run) is transmitted
to the indoor unit
OFF Always
OFF
OFF is transmitted
to the indoor unit
SW3-2
Initialization switch of
the air conditioners units
ON
Connected cancellatio
command is transmitted to
the indoor unit
OFF Always
OFF None
Notes:
*1:
Always use together with the local remote controller or system controller.
*2: Always register the LM ADAPTER as a system controller when using together with the system controller.
*3: The functions used with the LM ADAPTER are changed. The air conditioner and LOSSNAY cannot be set to interlock with the LM ADAPTER.
Set with the system controller or local remote controller.
*4: Carry out an instruction input at the unit of the lowest address unit in the same group. The instructions to other units are disregarded.
However, a state output is output for every unit. Forced thermostat OFF needs an instruction input for every unit.
*5: Input the same instructions to all the units in the same group.
*6: Make a monitor interval into 1 minute, and when you use both the functions of "local prohibit", and the "forced thermostat OFF", give 25 sets or less.
WLN02-2124 - 2 -