TheERVandHRVunitsareequippedwithanautomaticdefrostfeaturetoeliminateanyicebuildupon
thecore.
• Automaticdefrostisinitiatedonceeveryhourwhenthefreshairsupplytemperaturedropsto23°F
(-5°C)orcolder.
• Thedefrostcycleoperatesbyturningoffthesupplyfanwhilecontinuingtooperatetheexhaustfan.
• Theexhaustfanspeedisadjustedproportionallybasedontheoutdoortemperature,initiallyoperating
atlowspeed.
• Astheoutdoortemperaturecontinuestodrop,theexhaustfanspeedwillincrease,andwilloperateat
maximumspeedwhentheoutdoortemperatureis-4°F(-20°C)orless.
• Defrostcyclerunsfor4minuteswiththesupplyfanoff,followedby40minutesofcontinuousnormal
operation.
• Defrostcycleswillcontinuetorepeataslongasthetemperatureis23°F(-5°C)orless.