26 Generac
®
Power Systems, Inc.
6.3.2 TESTING THE INSTALLATION
Generac recommends testing the installation to be
sure adequate cooling airflow is available to the unit
before placing the unit into service. If the unit shows
signs of overheating, you will need to enlarge the air
openings. Never place a unit into service until
absolutely certain that cooling and ventilation is ade-
quate.
NOTE:
You must test the installation, especially if you
bring in air from below the generator set.
6.4 GASOLINE FUEL SYSTEM
Gasoline is highly flammable, and its vapors are
explosive. Comply with all codes, standards and
regulations pertaining to gasoline fuel systems
used in recreational vehicle generators.
Properly install and maintain the fuel system
and keep it entirely free of leaks. Gasoline
vapors must not enter the vehicle interior.
The installation of a gasoline fuel system (Figure
6.14) for a recreational vehicle generator set must
comply with applicable codes, standards and regula-
tions. The entire fuel system must be completely free
of leaks. There must be no possibility of gasoline
vapors entering the vehicle interior.
Figure 6.14 – Generator Fuel System
74.
.
21.
.
.
4.
.
.
.
44.
.
.
.
4.
.
OBSTRUCTIONS. ALL OPEN AREA IS RE