—32—
Table 6 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates alternate drive package only.
††Indicates high-static motor and drive package.
***Indicates alternate motor and drive package.
Table 7 — Evaporator-Fan Motor Efficiency
NOTE: Convert bhp to watts using the following formula:
Table 8 — Accessory/FIOP Static Pressure* (in. wg)
LEGEND *The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.
UNIT
558F
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
090,091† 840 815 790 765 740 715 690 665 635 615 590 — —
090,091** 935 910 885 860 835 810 785 760 735 710 685 — —
090,091†† 1080 1025 1007 988 970 952 933 915 897 878 860 — —
102,103† 935 910 885 860 835 810 785 760 735 710 685 — —
102,103†† 1080 1025 1007 988 970 952 933 915 897 878 860 — —
120,121† 935 910 885 860 835 810 785 760 735 710 685 — —
120,121*** 1085 1060 1035 1010 985 960 935 910 885 860 835 — —
120,121†† 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
150,151† 1080 1060 1035 1015 990 970 950 925 905 880 860 — —
150,151*** 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
MOTOR EFFICIENCY (%)
558F090-121
558F150,151
80
87
watts =
bhp (746)
motor efficiency
COMPONENT
CFM
2250 2500 3000 3500 4000 4500 5000 5500 6000 6250
1 Heater Module 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.17
2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21 0.20
Vertical EconoMi$er IV 0.06 0.075 0.115 0.15 0.195 0.25 0.325 — — —
Horizontal EconoMi$er IV — 0.10 0.15 0.21 0.275 0.34 — — — —
FIOP — Factory-Installed Option