—5—
SPECIFICATIONS Continued
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If
other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is
used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Fan motor with ball bearings required.
†† See low-ambient controller Installation Instructions for application.
N/A — Not Applicable.
NOTE:
Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
UNIT SIZE-SERIES 042-F 048-F 060-F
Operating Weight (Lb) 213 215 278
ELECTRICAL
Unit Volts—Hertz—Phase 208/230—60—1
Operating Voltage Range* 187—253
Compressor—Rated Load Amps 18.6 20.5 27.6
Locked Rotor Amps 105.0 109.0 158.0
Condenser Fan Motor—Full Load Amps 1.1 1.1 1.4
Min Unit Ampacity for Wire Sizing 24.4 26.7 35.9
Min Wire Size (60°C Copper) AWG† 10 10 8
Min Wire Size (75°C Copper) AWG† 10 10 8
Max Wire Length (Ft) (60°C Copper)‡ 81 74 86
Max Wire Length (Ft) (75°C Copper)‡ 77 71 82
Max Branch Circuit Fuse or
Circuit Breaker Size (Amps) 40 40 60
COMPRESSOR & REFRIGERANT
Compressor—Type Scroll
Temperature & Current Protection Internal Line Break
Refrigerant—Type Puron® (R-410A)
Amount (Lb) 5.43 5.75 8.00
CONDENSER COIL & FAN
Coil Face Area (Sq Ft) 12.2 12.2 18.2
Fins per In.—Rows—Circuits 25—1—225—1—225—1—3
Fan Motor—HP (PSC) & RPM 1/5 & 825 1/5 & 1100 1/4 & 1100
Volts—Hertz—Phase 208/230—60—1
Condenser Airflow (CFM) 2800 2800 3300
OPTIONAL EQUIPMENT
Support Feet KSASF0101AAA
Coastal Filter KAACF0801MED
Time Delay Relay KAATD0101TDR
Cycle Protector KSACY0101AAA
Crankcase Heater KAACH1201AAA
Start Assist—Capacitor/Relay Type KSAHS1501AAA KSAHS1601AAA
Start Assist—PTC Type KAACS0201PTC
TXV (Hard Shutoff) KSATX0301PUR KSATX0401PUR KSATX0501PUR
Piston Body KSAPX0101PIS
Filter Drier (Suction Line) KH45LG141 (RCD)
Evaporator Freeze Thermostat†† KAAFT0101AAA
Liquid-Line Solenoid Valve KAALS0201LLS
Winter Start Control†† KAAWS0101AAA
Low-Ambient Pressure Switch KSALA0301410
MotorMaster® Control** 32LT660004 (RCD)
Ball Bearing Fan Motor HC38GE231 (RCD) HC40GE232 (RCD)
Thermostat—Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool TSTATBBNAC01-B
Thermostat—Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool TSTATBBPAC01-B
Thermidistat™ Control—
Programmable Thermostat with Humidity Control TSTATBBPRH01-B
Builder’s Thermostat—Manual Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool TSTATBBBAC01-B
Outdoor Air Temperature Sensor TSTATXXSEN01-B
Backplate for Non-Programmable Thermostat TSTATXXNBP01
Backplate for Programmable Thermostat TSTATXXPBP01
Backplate for Builder’s Thermostat TSTATXXBBP01
Thermostat Conversion Kit (4 to 5 wire)—10 Pack TSTATXXCNV10