6. Inspect components to ensure the following
(continued):
c. The conductive rubber strip must be in
contact with the conductive-coated tips of
the media. See Figure 12.
d. The nine ionizing wires must be clean,
straight, and hooked onto the bus bar at
one end and the ionizer frame at the other.
See Figure 11.
e. The control electrode must be properly
inserted in the ionizer frame.
f. There must be no debris bridging the gap
between the ionizing wires and any other
component.
7. If a Model 51 is used:
a. Measure the current for the wire under the
bracket - this must be 4 amps or more.
b. Ensure the Model 51 is at least 4” away
from any transformer.
8. Re-install the inner housing assembly
and close the power pack / door assembly.
9. Plug in the unit and turn it on.
10. Turn on the furnace/air handler blower.
11. After the blower starts, check unit for proper
operation.
TROUBLE SHOOTING GUIDE (CONTINUED)