Omega Engineering FGM220 Building Set User Manual


 
TROUBLESHOOTING
Problem
Probable Causes Try...
Analog output at 0 mA
Analog output is 4 mA
with ow
No pulse output
Flow rate incorrect
4-20 mA loop needs an external power
supply - if missing, add it
Connect to earth ground
Note ow direction arrow, reverse direction
to match
Change output connection
Connect to earth ground
Change ow direction
Check for proper grounding
Select another ow meter
Install meter in vertical position
No loop power
Unit not grounded
Flow reversed
Reversed output connections
Not grounded
Reversed ow
Missing or incorrect ground wire
Fluid conductivity <20 microSiemens/cm
Empty pipe