The external, manually operated bypass unit is an option for the
PROTECT C.6000R UPS series in a rack version with 2U. It is
used for disconnecting the UPS, for example for maintenance
purposes, whilst the connected loads continue to be supplied
without interruption. As well as solely bypass operation, an
additional switch setting permits UPS test operation. Separately
fused non-heating appliance connectors make it possible for the
loads to be supplied directly from the MBS 6000. LEDs with
various colours clearly signal which operating status has been
selected.
Scope of delivery:
External bypass unit MBS 6000
2 connection cables to the UPS
Operating instructions
Prerequisite:
AEG UPS in the PROTECT C.6000R series
Technical data:
Nominal connection voltage /
- frequency
230 VAC 50/60 Hz
Nominal current 32 A
Number of output sockets
(load connection)
8 x IEC 320 C13 (10 A),
fused in pairs
by miniature fuse
5 x 20 mm, T
10 A
additional non-fused
output on terminal
Housing colour blackline
Dimensions (HxWxD)
19-inch / rack operation
88 mm x 483 mm x 350 mm
2
U x 19"